LC1D12N7

TeSys Deca contactor - 3P(3 NO) - AC-3/AC-3e - <= 440 V 12 A - 415 V AC coil
In stock, ship within 3-5 days
Quantity
ADD TO CART
BUY IT NOW
Detail
Customer Reviews
Main
Range of Product TeSys Deca
Product or Component Type Contactor
Device short name LC1D
contactor application Motor control
Resistive load
utilisation category AC-1
AC-4
AC-3
AC-3e
Poles description 3P
[Ue] rated operational voltage Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current 25 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
12 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
12 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage 415 V AC 50/60 Hz
Complementary
Motor power kW 3 kW at 220...230 V AC 50/60 Hz (AC-3)
5.5 kW at 380...400 V AC 50/60 Hz (AC-3)
5.5 kW at 415...440 V AC 50/60 Hz (AC-3)
7.5 kW at 500 V AC 50/60 Hz (AC-3)
7.5 kW at 660...690 V AC 50/60 Hz (AC-3)
3.7 kW at 400 V AC 50/60 Hz (AC-4)
3 kW at 220...230 V AC 50/60 Hz (AC-3e)
5.5 kW at 380...400 V AC 50/60 Hz (AC-3e)
5.5 kW at 415...440 V AC 50/60 Hz (AC-3e)
7.5 kW at 500 V AC 50/60 Hz (AC-3e)
7.5 kW at 660...690 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating 0.5 hp at 115 V AC 50/60 Hz for 1 phase motors
2 hp at 230/240 V AC 50/60 Hz for 1 phase motors
3 hp at 200/208 V AC 50/60 Hz for 3 phase motors
3 hp at 230/240 V AC 50/60 Hz for 3 phase motors
7.5 hp at 460/480 V AC 50/60 Hz for 3 phase motors
10 hp at 575/600 V AC 50/60 Hz for 3 phase motors